In short
Where the Planning and Design Code's Stormwater Management Overlay applies, a new home's rainwater tank is sized by site area: 1,000 L, 2,000 L or 4,000 L of retention, plus 1,000 L of detention on small or mostly hard-surfaced sites, released through a 20–25 mm orifice. The old building-rule 1 kL tank no longer applies, and kerb connections need council approval.
Key takeaways
- Retention: 1,000 L under 200 m², 2,000 L for 200–400 m², 4,000 L from 401 m². Detention of 1,000 L is added on small or low-perviousness sites.
- SA Part H9, the old building-rule 1 kL tank, does not apply in South Australia any more. The Code overlay sets tank sizes now.
- Connecting to the kerb needs council approval. Councils set pipe sizes, outlet spacing and distances from street trees.
- On reactive clay, water in the wrong place moves footings. Drainage is part of the structure, not an afterthought.
Close to half of Australia's searches for "drainage plan" come from South Australia, and for good reason. Councils ask for one with many building applications, the tank rules changed recently, and on Adelaide's reactive clay, water in the wrong place cracks houses.
Stormwater rules: quick facts
- Retention tank
- 1,000 / 2,000 / 4,000 L by site area
- Detention
- 1,000 L on small or low-perviousness sites
- Orifice
- 20–25 mm slow release
- Old 1 kL rule
- SA Part H9 no longer applies
- Kerb connection
- Council approval needed
- Our drainage plans
- From $790 + GST ($869 inc GST)
How big does a rainwater tank need to be in Adelaide?
The tank size depends on your site area: 1,000 L of retention under 200 m², 2,000 L for 200–400 m², and 4,000 L for 401 m² or more. These are the deemed-to-satisfy volumes in the Code's Stormwater Management Overlay (DTS/DPF 1.1, Table 1).
Rainwater retention required by site area
The overlay applies to detached, semi-detached and row dwellings, groups of fewer than 5 dwellings, co-located housing and flat dwellings. To meet it, the tank also has to:
- Collect from at least 60% of the roof for a detached (not battle-axe), semi-detached or row dwelling, and 80% for other types
- Be plumbed to a toilet or the laundry cold water outlets on sites under 200 m², or to one toilet and the laundry cold outlets on 200 m² and over
- Have a 20–25 mm slow-release orifice wherever detention is required
The dwelling's roof must also make up at least 80% of the site's hard (impervious) area. The overlay isn't mapped everywhere, so check your address in the SA Property and Planning Atlas (SAPPA) or on PlanSA.
What is stormwater detention, and how is it different from retention?
Detention holds water back for a short time and releases it slowly; retention keeps it for use. A detention tank, or the top part of a combined tank, fills during a storm and drains out through the small orifice over the following hours.
| Retention | Detention | |
|---|---|---|
| Purpose | Reuse in toilets and laundry | Slow the peak flow to the street |
| Volume | 1,000–4,000 L by site area | 1,000 L where required |
| Outlet | Pump and plumbing to fixtures | 20–25 mm orifice to the stormwater system |
| When it's empty | Rarely: you use it down | Soon after each storm |
Perviousness is the share of your site that soaks up rain, such as lawn and garden beds. Large houses, driveways and paved yards on small blocks push it down, which is why detention is required more often on infill sites. MBS 009 "On-site retention of stormwater" sets out cost-effective solutions, and Green Adelaide is preparing guidance on meeting the Code's stormwater requirements.
Does the 1,000 L rainwater tank rule still apply in SA?
No. The old building-rule requirement for a plumbed 1 kL tank came from SA Part H9, a South Australian variation to the National Construction Code. MBS 007 Amendment 5 (December 2025) and Amendment 6 (April 2026) both state that "SA Part H9 does not apply in South Australia".
Why you still see the old rule
Even under NCC 2022, SA H9 only applied to HomeBuilder grant development. The sa.gov.au rainwater tank page, last updated in December 2023, still describes the old 1 kL rule. For a house today, the Stormwater Management Overlay sets the tank size, and your consent conditions are what count.
Can I connect stormwater to the kerb in Adelaide?
Yes, with council approval. Each council sets its own conditions. In Holdfast Bay, for example, the owner is responsible for the pipe through the verge and the outlet in the kerb.
| Council example | What it requires |
|---|---|
| Holdfast Bay | Section 221 (Local Government Act) application, $80 fee. Pipes 75–100 mm, one outlet per 10 m of frontage (up to 2 × 100 mm side by side), at least 2 m from street trees and 0.2 m from inverts |
| Unley (policy reported December 2025) | All stormwater to the kerb water table, none onto footpaths, up to 20 L/s per connection, outlets at least 20 m apart, no groundwater to the kerb |
| Lots below road level | Gravity to the kerb may not work: grated drains, a pump or on-site detention are needed |
Holdfast Bay from its connection form page. Unley from a secondary summary of its December 2025 policy; confirm current conditions with your council.
What are the rules for building near an SA Water easement?
You can't build over an SA Water water easement or a sewer access point, and anything over a sewer easement has clearance rules. Applications go to SA Water at the same time as council.
- A house over an easement but not over a main: footing zone of influence clear of the trench, 1.5 m to the main's centre, concrete in 1.0 m slabs within 0.6 m of the main's centreline, and a maximum length of 6.5 m.
- Sheds and carports: 1.0 m clearance if demountable, 1.5 m if masonry. Over a main they must be demountable, with 2.4 m openings for access.
- Pools and tanks in an easement must keep the footing zone of influence clear of the sewer trench.
SA Water's encroachment fact sheet is undated, so confirm the current requirements with SA Water before you finalise a design.
Why does stormwater matter for footings on reactive clay?
Because water changes the volume of reactive clay. Much of Adelaide sits on highly reactive clay; every site needs its own classification. Clay that gets wet swells and lifts footings (heave), and clay that dries shrinks and lets them drop.
The 2016 Modbury North soil study found the clays there react to ponding and leaking service pipes, with significant surface heave in wet months. The same thing happens around the city when downpipes discharge at the wall, overflows dump next to the footings, or paths fall towards the house.
Do
- Pipe every downpipe and tank overflow to the street system or an approved outlet
- Grade paving and garden beds to fall away from the walls
- Fix leaking stormwater and sewer pipes quickly
Don't
- Let a downpipe or overflow discharge against the footing
- Install air drains in reactive clay without geotechnical engineering advice
- Assume the old drainage still works after an extension or new paving
What does a stormwater or drainage plan show?
A drainage plan shows where every litre of roof and surface water goes, at what size and fall, and how it leaves the site. Councils and certifiers ask for one with many building applications, and it is what your plumber builds from.
- Roof catchments, downpipes and the share of roof connected to the tank
- Tank sizes for retention and detention, with the orifice and overflow
- Pipe sizes, falls and pits, with levels from the house to the outlet
- The kerb outlet location, or a pump or detention solution for low lots
- Easements, existing services and clearances to footings and street trees
Our stormwater and drainage plans start from $790 + GST ($869 inc GST). Many go with new footings or a granny flat: see site classification and footings and granny flat engineering.
When should you call a structural engineer about stormwater?
- Council or your certifier has asked for a stormwater management or drainage plan
- You're building on a small or infill site where detention is likely to be required
- The block sits below the road, so water can't fall to the kerb
- Cracks appeared after wet weather or near a leaking pipe. See cracks in walls
- You want to build near an SA Water easement and need the footing clearances designed
What to send
A site plan, the roof plan and any council request. Get a fixed quote in under 20 minutes on average, during business hours, or call 08 7083 9853.
Need an engineer?
Need a stormwater or drainage plan?
Send the site plan and roof plan. You get a fixed quote in under 20 minutes on average, during business hours.
Sources
- PlanSA, Planning and Design Code, Version 2026.19 (8 October 2026). Stormwater Management Overlay, DTS/DPF 1.1 and Table 1. Check the online Code for the current version
- PlanSA, MBS 007 Modifications to the Building Code of Australia for NCC 2022 (Amendment 6, April 2026). "SA Part H9 does not apply in South Australia"
- Australian Building Codes Board, NCC 2022 Volume Two, SA Part H9 Water efficiency
- PlanSA, Ministerial Building Standards. MBS 009 On-site retention of stormwater
- City of Holdfast Bay, Stormwater pipe connection form
- SA Water, Encroachment over easement (fact sheet)